specifcations voltage input full range mode 400 v 250 v 120 v input voltage ac (v rms ) 0 ~ 400 0 ~ 250 0 ~ 120 dc (v) 0 ~ 400 0 ~ 250 0 ~ 120 input impedance 48 k 30 k 14.4 k voltage output ? output signal 0 ~ 5 v dc ? accuracy < 1.0 % for full range ? output impedance < 10 ? @ operating frequency <60 hz ? load > 10 k ? ? ripple < 120mvp-p ? temperature 400 ppm/c coeffcient ? input bandwidth 6 khz power consumption ? supply voltage 24 v dc 10 % ? current consumption 40 ma general ? isolation protection 1,000 v dc (output to power) 2,500 v rms (input to output, input to power) ? operating 0 ~ 60c (32 ~ 140f) temperature ? storage temperature -20 ~ 70c (-4 ~ 158f) ? storage humidity 5 ~ 95 % ordering information ? adam-3112 isolated ac voltage input module adam-3016 adam-3112 adam-3114 specifcations current input ? ac current input 0 ~ 5 a rms ? dc current input 0 ~ 5 a voltage output ? output signal 0 ~ 5 v dc ? accuracy < 1.0 % for full range ? output impedance <10 ? @ operating frequency <60 hz ? load > 10 k? ? ripple < 120 mvp-p ? temperature 400 ppm/c coeffcient ? input bandwidth 10 khz power consumption ? supply voltage 24 v dc 10 % ? current consumption 40 ma general ? isolation protection 1,000 v dc (output to power) 2,500 v rms (input to output, input to power) ? operating 0 ~ 60c (32 ~ 140f) temperature ? storage temperature -20 ~ 70c (-4 ~ 158f) ? storage humidity 5 ~ 95 % ordering information ? adam-3114 isolated ac current input module isolated strain gauge input module isolated ac voltage input module isolated ac current input module adam-3112 adam-3114 specifcations i/o ? accuracy 0.1% of full range ? bandwidth 2.4 khz (typical) ? isolation mode >100 db @ 50 hz/60 hz rejection ? current output current: 0 ~ 20 ma current load resistor: 0 ~ 500 ? (source) ? stability 150 ppm (typical) (temperature drift) ? voltage electrical input: 10 mv, specifcations 20 mv, 30 mv, 100 mv excitation voltage: 1 ~ 10 v dc (60 ma max) ? voltage output bipolar: 5 v, 10 v unipolar: 0 ~ 10 v impedance: < 50 ? general ? connectors screw terminal ? enclosure abs ? indicators power led indicator ? isolation 1,000 v dc (three-way) ? power 1.85 w (voltage output) consumption 2.15 w (current output) ? power input 24 v dc 10% ? operating -10 ~ 70c (14 ~ 158f) temperature ? storage -25 ~ 85c (-13 ~ 185f) temperature ordering information ? adam-3016 isolated strain gauge input module adam-3016 all product specifications are subject to change without notice last updated : 5-may-2015 www.advantech.com/products online download
|