product data sheet 3RT1066-6AP36 contactor, 160kw/400v/ac-3 ac(40...60hz)/dc operation uc 220- 240v auxiliary contacts 2no+2nc 3-pole, size s10 bar connections convent. operating mechanism screw terminal general technical data: product brand name sirius size of the contactor s10 protection class ip / on the front ip00 degree of pollution 3 installation altitude / at a height over sea level / maximum m 2,000 ambient temperature / during operating c -25 ? +60 mechanical operating cycles as operating time ? of the contactor / typical 10,000,000 ? of the contactor with added auxiliary switch block / typical 10,000,000 ? of the contactor with added electronics-compatible auxiliary switch block / typical 5,000,000 main circuit: number of nc contacts / for main contacts 0 number of no contacts / for main contacts 3 operating current ? at ac-1 / at 400 v ? at 40 c ambient temperature / rated value a 330 ? at 60 c ambient temperature / rated value a 300 ? at ac-3 / at 400 v / rated value a 300 3RT1066-6AP36 page 1/ 09/28/2012 subject to modifications ? copyright siemens ag 2012 6 http:// http://
? at ac-4 / at 400 v / rated value a 280 ? with 1 current path / at dc-1 ? at 24 v / rated value a 300 ? at 110 v / rated value a 33 ? with 2 current paths in series / at dc-1 ? at 24 v / rated value a 300 ? at 110 v / rated value a 300 ? with 3 current paths in series / at dc-1 ? at 24 v / rated value a 300 ? at 110 v / rated value a 300 ? with 1 current path / at dc-3 / at dc-5 ? at 24 v / rated value a 300 ? at 110 v / rated value a 3 ? with 2 current paths in series / at dc-3 / at dc-5 ? at 24 v / rated value a 300 ? at 110 v / rated value a 300 ? with 3 current paths in series / at dc-3 / at dc-5 ? at 24 v / rated value a 300 ? at 110 v / rated value a 300 service power ? at ac-2 / at 400 v / rated value kw 171 ? at ac-3 / at 400 v / rated value kw 171 ? at ac-4 / at 400 v / rated value w 160,000 active power loss / per conductor / typical w 22 control circuit: design of the surge suppressor with varistor type of voltage / of the controlled supply voltage ac/dc control supply voltage / 1 ? for dc ? initial rated value v 220 ? final rated value v 240 ? at 50 hz / for ac ? initial rated value v 220 ? final rated value v 240 ? at 60 hz / for ac ? initial rated value v 220 ? final rated value v 240 operating range factor control supply voltage rated value / of the magnet coil 3RT1066-6AP36 page 2/ 09/28/2012 subject to modifications ? copyright siemens ag 2012 6
? at 50 hz ? for ac 0.8 ? 1.1 ? at 60 hz ? for ac 0.8 ? 1.1 ? for dc 0.8 ? 1.1 apparent pull-in power / of the solenoid / for ac va 590 apparent holding power / of the solenoid / for ac va 6.7 inductive power factor / with the pull-in power of the coil 0.9 inductive power factor / with the pull-in power of the coil 0.9 pull-in power / of the solenoid / for dc w 650 holding power / of the solenoid / for dc w 7.4 auxiliary circuit: contact reliability / of the auxiliary contacts 1 faulty switching per 100 million (17 v, 1 ma) number of nc contacts / for auxiliary contacts / instantaneous switching 2 number of no contacts / for auxiliary contacts / instantaneous switching 2 operating current / of the auxiliary contacts ? at ac-12 / maximum a 10 ? at ac-15 ? at 230 v a 6 ? at 400 v a 3 ? at dc-12 ? at 60 v a 6 ? at 110 v a 3 ? at 220 v a 1 ? at dc-13 ? at 24 v a 10 ? at 60 v a 2 ? at 110 v a 1 ? at 220 v a 0.3 short-circuit: design of the fuse link ? for short-circuit protection of the auxiliary switch / required fuse gl/gg: 10 a ? for short-circuit protection of the main circuit ? with type of assignment 1 / required fuse gl/gg: 500 a ? at type of coordination 2 / required fuse gl/gg: 400 a installation/mounting/dimensions: type of mounting screw fixing 3RT1066-6AP36 page 3/ 09/28/2012 subject to modifications ? copyright siemens ag 2012 6
series installation yes width mm 145 height mm 210 depth mm 202 distance, to be maintained, to earthed part / sidewards mm 10 connection type: design of the electrical connection ? for main current circuit screw-type terminals ? for auxiliary and control current circuit screw-type terminals type of the connectable conductor cross-section ? for awg conductors / for main contacts 2/0 ... 500 kcmil ? for auxiliary contacts ? solid 2x (0.5 ... 1.5 mm2), 2x (0.75 ... 2.5 mm2), max. 2x (0.75 ... 4 mm2) ? finely stranded ? with conductor end processing 2x (0.5 ... 1.5 mm2), 2x (0.75 ... 2.5 mm2) ? for awg conductors / for auxiliary contacts 2x (20 ... 16), 2x (18 ... 14), 1x 12 certificates/approvals: general product approval functional safety / safety of machinery declaration of conformity type examination test certificates shipping approval other special test certificate other confirmation other environmental confirmations further information: information- and downloadcenter (catalogs, brochures,?) http://www.siemens.com/industrial-controls/catalogs industry mall (online ordering system) http://www.siemens.com/industrial-controls/mall cax online generator: http://www.siemens.com/cax service&support (manuals, certificates, characteristics, faqs,...) http://support.automation.siemens.com/ww/view/en/3RT1066-6AP36/all 3RT1066-6AP36 page 4/ 09/28/2012 subject to modifications ? copyright siemens ag 2012 6
image database (product images, 2d dimension drawings, 3d models, device circuit diagrams, ...) http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3RT1066-6AP36 3RT1066-6AP36 page 5/ 09/28/2012 subject to modifications ? copyright siemens ag 2012 6
last change: sep 24, 2012 3RT1066-6AP36 page 6/ 09/28/2012 subject to modifications ? copyright siemens ag 2012 6
|