  Datasheet File OCR Text:
  r-rated fuses for motor circuit protection medium voltage bussmann catalog symbol: jck, jck-a, jck-b, jch, jcl, jcl-a, jcl-b, jcg, jcr-a, & jcr-b r-rated medium voltage current limiting 2400v ac jck, jck-a, jck-b, jch 4800v ac jcl, jcl-a, jcl-b, jcg 7200v ac jcr-a, jcr-b max. design voltage 2540v ac jck, jck-a, jck-b, jch 5080v ac jcl, jcl-a jcl-b, jcg 8300v ac jcr-a, jcr-b ul recognized: 2540v ac jck, jck-a 5080v ac jcl, jcl-a (2r-24r) ul recognized (guide #msss2, file # e96676) ? r-rated medium voltage fuses are back-up current limiting fuses used in conjunction with medium voltage motors and motor controllers. ? the jck-a, jcl-a, & jcr-a are supplied with cutler- hammer ampgard hookeye. ? this single hookeye is on one end of the fuse and aids in the insertion and removal of the fuse. ? current limiting fuses may be designated as r-rated if they meet the following requirements: 1. the fuse will safely interrupt all currents between its minimum and maximum interrupting ratings. 2. the fuse will melt in a range of 15 to 35 seconds at a value of 100 times the r number (ansi c37.46). ? bussmann r-rated current limiting fuses are designed for use with medium voltage starters to provide short-circuit protection for the motor and motor controller. ? these fuses offer a high level of fault current interruption in a self-contained, non-venting package which can be mounted indoors or in an enclosure. ? open fuse indication on all fuses. jck, jck-a, jck-b, jch, jcl, jcl-a, jcl-b, jcg, jcr-a, & jcr-b 2-26-03 sb03044 form no. jck, jck-a, jck-b, jch, jcl, jcl-a, jcl-b, jcg, jcr-a, & jcr-b page 1 of 8 data sheet: 6001
specifications buss maximum dimensions (inches) max. int. cap. min. int. cap. catalog no. amperage design voltage a b c construction amps (asym.) amps (sym.) amps (sym.) 2400v; r-rated; indoor/enclosure (see figure 1) jck-2r 70 2r 2540v 11.24 3.0 3.0 single 80,000 50,000 165 jck-3r 100 3r 2540v 11.24 3.0 3.0 single 80,000 50,000 220 jck-4r 130 4r 2540v 11.24 3.0 3.0 single 80,000 50,000 320 jck-5r 150 5r 2540v 11.24 3.0 3.0 single 80,000 50,000 410 jck-6r 170 6r 2540v 11.24 3.0 3.0 single 80,000 50,000 480 jck-9r 200 9r 2540v 11.24 3.0 3.0 single 80,000 50,000 720 jck-12r 230 12r 2540v 11.24 3.0 3.0 single 80,000 50,000 970 jck-18r 390 18r 2540v 11.24 3.0 3.0 double 80,000 50,000 1,430 jck-24r 450 24r 2540v 11.24 3.0 3.0 double 80,000 50,000 1,880 2400v; r-rated; indoor/enclosure; with cutler-hammer ampgard hookeye (see figure 1) jck-a-2r 70 2r 2540v 11.24 3.0 3.0 single 80,000 50,000 165 jck-a-3r 100 3r 2540v 11.24 3.0 3.0 single 80,000 50,000 220 jck-a-4r 130 4r 2540v 11.24 3.0 3.0 single 80,000 50,000 320 jck-a-5r 150 5r 27540v 11.24 3.0 3.0 single 80,000 50,000 410 jck-a-6r 170 6r 2540v 11.24 3.0 3.0 single 80,000 50,000 480 jck-a-9r 200 9r 2540v 11.24 3.0 3.0 single 80,000 50,000 720 jck-a-12r 230 12r 2540v 11.24 3.0 3.0 single 80,000 50,000 970 JCK-A-18R 390 18r 2540v 11.24 3.0 3.0 double 80,000 50,000 1,430 jck-a-24r 450 24r 2540v 11.24 3.0 3.0 double 80,000 50,000 1,880 2400v; r-rated; indoor/enclosure; bolt-on (see figure 2) jck-b-30 25 2540v 14.18 12.81 - single 80,000 50,000 100 jck-b-2r 70 2r 2540v 14.18 12.81 - single 80,000 50,000 180 jck-b-3r 100 3r 2540v 14.18 12.81 - single 80,000 50,000 270 jck-b-4r 130 4r 2540v 14.18 12.81 - single 80,000 50,000 360 jck-b-5r 150 5r 2540v 14.18 12.81 - single 80,000 50,000 450 jck-b-6r 170 6r 2540v 14.18 12.81 - single 80,000 50,000 540 jck-b-9r 200 9r 2540v 14.18 12.81 - single 80,000 50,000 740 jck-b-12r 230 12r 2540v 14.18 12.81 - single 80,000 50,000 1,080 jck-b-18r 390 18r 2540v 14.18 12.81 3.56 double 80,000 50,000 1,500 jck-b-24r 450 24r 2540v 14.18 12.81 3.56 double 80,000 50,000 2,200 2400v; r-rated; indoor; hermetically sealed, class 1, group d, div. 2, hazardous locations; for use with ampgard motor starters (see figure 1) jch-30 25 2540v 11.56 3.0 4.12 single 80,000 50,000 100 jch-2r 70 2r 2540v 11.56 3.0 4.12 single 80,000 50,000 180 jch-3r 100 3r 2540v 11.56 3.0 4.12 single 80,000 50,000 270 jch-4r 130 4r 2540v 11.56 3.0 4.12 single 80,000 50,000 360 jch-5r 150 5r 2540v 11.56 3.0 4.12 single 80,000 50,000 450 jch-6r 170 6r 2540v 11.56 3.0 4.12 single 80,000 50,000 540 jch-9r 200 9r 2540v 11.56 3.0 4.12 single 80,000 50,000 740 jch-12r 230 12r 2540v 11.56 3.0 4.12 single 80,000 50,000 1,080 jch-18r 390 18r 2540v 11.56 3.0 7.68 double 80,000 50,000 1,500 jch-24r 450 24r 2540v 11.56 3.0 7.68 double 80,000 50,000 2,200 4800v; r-rated; indoor/enclosure (see figure 1) jcl-2r 70 2r 5080v 15.76 3.0 3.0 single 80,000 50,000 165 jcl-3r 100 3r 5080v 15.76 3.0 3.0 single 80,000 50,000 220 jcl-4r 130 4r 5080v 15.76 3.0 3.0 single 80,000 50,000 320 jcl-5r 150 5r 5080v 15.76 3.0 3.0 single 80,000 50,000 410 jcl-6r 170 6r 5080v 15.76 3.0 3.0 single 80,000 50,000 480 jcl-9r 200 9r 5080v 15.76 3.0 3.0 single 80,000 50,000 720 jcl-12r 230 12r 5080v 15.76 3.0 3.0 single 80,000 50,000 970 jcl-18r 390 18r 5080v 15.76 3.0 3.0 double 80,000 50,000 1,430 jcl-24r 450 24r 5080v 15.76 3.0 3.0 double 80,000 50,000 1,880 2-26-03 sb03044 bussmann r-rated fuses for motor circuit protection medium voltage jck, jck-a, jck-b, jch, jcl, jcl-a, jcl-b, jcg, jcr-a, & jcr-b form no. jck, jck-a, jck-b, jch, jcl, jcl-a, jcl-b, jcg, jcr-a, & jcr-b page 2 of 8 data sheet: 6001
specifications buss maximum dimensions (inches) max. int. cap. min. int. cap. catalog no. amperage design voltage a b c construction amps (asym.) amps (sym.) amps (sym.) 4800v; r-rated; indoor/enclosure; with cutler-hammer ampgard hookeye (see figure 1) jcl-a-2r 70 2r 5080v 15.76 3.0 3.0 single 80,000 50,000 165 jcl-a-3r 100 3r 5080v 15.76 3.0 3.0 single 80,000 50,000 220 jcl-a-4r 130 4r 5080v 15.76 3.0 3.0 single 80,000 50,000 320 jcl-a-5r 150 5r 5080v 15.76 3.0 3.0 single 80,000 50,000 410 jcl-a-6r 170 6r 5080v 15.76 3.0 3.0 single 80,000 50,000 480 jcl-a-9r 200 9r 5080v 15.76 3.0 3.0 single 80,000 50,000 720 jcl-a-12r 230 12r 5080v 15.76 3.0 3.0 single 80,000 50,000 970 jcl-a-18r 390 18r 5080v 15.76 3.0 3.0 double 80,000 50,000 1,430 jcl-a-24r 450 24r 5080v 15.76 3.0 3.0 double 80,000 50,000 1,880 jcl-a-36r 650 36r 5080v 16.0 4.0 - double 100,000 63,000 3,200 4800v; r-rated; indoor/enclosure; bolt-on (see figure 2) jcl-b-30 30 5080v 19.25 17.88 - single 80,000 50,000 100 jcl-b-2r 70 2r 5080v 19.25 17.88 - single 80,000 50,000 180 jcl-b-3r 100 3r 5080v 19.25 17.88 - single 80,000 50,000 270 jcl-b-4r 130 4r 5080v 19.25 17.88 - single 80,000 50,000 360 jcl-b-5r 150 5r 5080v 19.25 17.88 - single 80,000 50,000 450 jcl-b-6r 170 6r 5080v 19.25 17.88 - single 80,000 50,000 540 jcl-b-9r 200 9r 5080v 19.25 17.88 - single 80,000 50,000 740 jcl-b-12r 230 12r 5080v 19.25 17.88 - single 80,000 50,000 1,080 jcl-b-18r 390 18r 5080v 19.25 17.88 3.31 double 80,000 50,000 1,500 jcl-b-24r 450 24r 5080v 19.25 17.88 3.31 double 80,000 50,000 2,200 4800v; r-rated; indoor; hermetically sealed, class 1, group d, div. 2, hazardous locations; for use with ampgard motor starters (see figure 1) jcg-30 30 5080v 16.6 3.0 4.12 single 80,000 50,000 95 jcg-2r 70 2r 5080v 16.6 3.0 4.12 single 80,000 50,000 180 jcg-3r 100 3r 5080v 16.6 3.0 4.12 single 80,000 50,000 270 jcg-4r 130 4r 5080v 16.6 3.0 4.12 single 80,000 50,000 350 jcg-5r 150 5r 5080v 16.6 3.0 4.12 single 80,000 50,000 450 jcg-6r 170 6r 5080v 16.6 3.0 4.12 single 80,000 50,000 540 jcg-9r 200 9r 5080v 16.6 3.0 4.12 single 80,000 50,000 700 jcg-12r 230 12r 5080v 16.6 3.0 4.12 single 80,000 50,000 1,000 jcg-18r 390 18r 5080v 15.85 3.0 6.31 double 80,000 50,000 1,450 jcg-24r 450 24r 5080v 15.85 3.0 6.31 double 80,000 50,000 2,000 7200v; r-rated; indoor/enclosure; with ampgard hookeye (see figure 1) jcr-a-2r 70 2r 8300v 15.85 3.0 4.12 single 80,000 50,000 200 jcr-a-3r 100 3r 8300v 15.85 3.0 4.12 single 80,000 50,000 320 jcr-a-4r 130 4r 8300v 15.85 3.0 4.12 single 80,000 50,000 405 jcr-a-5r 150 5r 8300v 15.85 3.0 4.12 single 80,000 50,000 550 jcr-a-6r 170 6r 8300v 15.85 3.0 4.12 single 80,000 50,000 670 jcr-a-9r 200 9r 7200v 15.85 3.0 4.12 single 80,000 50,000 1,300 jcr-a-12r 230 12r 7200v 15.85 3.0 4.12 single 80,000 50,000 1,500 jcr-a-18r 390 18r 7200v 15.85 3.0 7.43 double 80,000 50,000 2,000 jcr-a-24r 450 24r 7200v 15.85 3.0 7.43 double 80,000 50,000 2,600 7200v; r-rated; indoor/enclosure; bolt-on (see figure 2) jcr-b-2r 70 2r 8300v 19.25 17.88 - single 80,000 50,000 200 jcr-b-3r 100 3r 8300v 19.25 17.88 - single 80,000 50,000 320 jcr-b-4r 130 4r 8300v 19.25 17.88 - single 80,000 50,000 405 jcr-b-5r 150 5r 8300v 19.25 17.88 - single 80,000 50,000 550 jcr-b-6r 170 6r 8300v 19.25 17.88 - single 80,000 50,000 670 jcr-b-9r 200 9r 7200v 19.25 17.88 - single 80,000 50,000 1,300 jcr-b-12r 230 12r 7200v 19.25 17.88 - single 80,000 50,000 1,500 jcr-b-18r 390 18r 7200v 19.25 17.88 3.31 double 80,000 50,000 2,000 jcr-b-24r 450 24r 7200v 19.25 17.88 3.31 double 80,000 50,000 2,600 bussmann r-rated fuses for motor circuit protection medium voltage jck, jck-a, jck-b, jch, jcl, jcl-a, jcl-b, jcg, jcr-a, & jcr-b 2-26-03 sb03044 form no. jck, jck-a, jck-b, jch, jcl, jcl-a, jcl-b, jcg, jcr-a, & jcr-b page 3 of 8 data sheet: 6001
bussmann r-rated fuses for motor circuit protection medium voltage jck, jck-a, jck-b, jch, jcl, jcl-a, jcl-b, jcg, jcr-a, & jcr-b 2-26-03 sb03044 form no. jck, jck-a, jck-b, jch, jcl, jcl-a, jcl-b, jcg, jcr-a, & jcr-b page 4 of 8 data sheet: 6001 0.38" (9.5mm) b indicator showing fuse is open indicator showing fuse is open a c dimensional data figure 1 figure 2
bussmann r-rated fuses for motor circuit protection medium voltage jck, jck-a, jck-b, jch, jcl, jcl-a, jcl-b, jcg, jcr-a, & jcr-b current limitation curves time-current characteristic curvesCminimum melt jck, jck-a, jcl, jcl-a 2-26-03 sb03044 184-a total clearing curves 168-a 167-a prospective short circuit current (x10) rms symmetrical amperes instantaneous peak let thru current amperes form no. jck, jck-a, jck-b, jch, jcl, jcl-a, jcl-b, jcg, jcr-a, & jcr-b page 5 of 8 data sheet: 6001
bussmann r-rated fuses for motor circuit protection medium voltage jck, jck-a, jck-b, jch, jcl, jcl-a, jcl-b, jcg, jcr-a, & jcr-b 2-26-03 sb03044 form no. jck, jck-a, jck-b, jch, jcl, jcl-a, jcl-b, jcg, jcr-a, & jcr-b page 6 of 8 data sheet: 6001 time-current curve: minimum melt time-current curve: total clearing jck-b, jch 50999-1 peak let-through curves 50999-3 50999-2 prospective short circuit current (x10) rms symmetrical amperes instantaneous peak let thru current amperes
bussmann 2-26-03 sb03044 form no. jck, jck-a, jck-b, jch, jcl, jcl-a, jcl-b, jcg, jcr-a, & jcr-b page 7 of 8 data sheet: 6001 r-rated fuses for motor circuit protection medium voltage jck, jck-a, jck-b, jch, jcl, jcl-a, jcl-b, jcg, jcr-a, & jcr-b time-current curve: minimum melt time-current curve: total clearing jcl-b, jcg 51000-1 peak let-through curves 51000-3 51000-2 prospective short circuit current (x10) rms symmetrical amperes instantaneous peak let thru current amperes
bussmann 2-26-03 sb03044 form no. jck, jck-a, jck-b, jch, jcl, jcl-a, jcl-b, jcg, jcr-a, & jcr-b page 8 of 8 data sheet: 6001 r-rated fuses for motor circuit protection medium voltage jck, jck-a, jck-b, jch, jcl, jcl-a, jcl-b, jcg, jcr-a, & jcr-b time-current curve: minimum melt time-current curve: total clearing jcr, jcr-b peak let-through curves the only controlled copy of this data sheet is the electronic read-only version located on the bussmann network drive. all oth er copies of this data sheet are by definition uncontrolled. this bulletin is intended to clear- ly present comprehensive product data and provide technical information that will help the end user with design applications. b ussmann reserves the right, without notice, to change design or construction of any prod- ucts and to discontinue or limit distribution of any products. bussmann also reserves the right to change or update, without no tice, any technical information contained in this bulletin. once a product has been selected, it should be tested by the user in all possible applications. 51001-1 51001-2 51001-3 prospective short circuit current (x10) rms symmetrical amperes instantaneous peak let thru current amperes


▲Up To Search▲   

 
Price & Availability of JCK-A-18R

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X