Part Number Hot Search : 
109M000 1H100 1N5239B 30Q6P45 DT25C01 2N5334 121206 SMB2K40
Product Description
Full Text Search
 

To Download SDR-240 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 240W Single Output Industrial DIN RAIL with PFC Function
Features :
SDR-240 series
High efficiency 94% and low power dissipation 150% peak load capability Built-in active PFC function, PF>0.93 Protections: Short circuit / Overload / Over voltage / Over temperature Cooling by free air convection Built-in constant current limiting circuit Can be installed on DIN rail TS-35/7.5 or 15 UL 508 (industrial control equipment) approved EN61000-6-2(EN50082-2) industrial immunity level Built-in DC OK relay contact 100% full load burn-in test 3 years warranty
SE
PQ
M
IF
GL
Marine
47
SPECIFICATION
MODEL DC VOLTAGE RATED CURRENT CURRENT RANGE RATED POWER PEAK CURRENT PEAK POWER Note.6 OUTPUT VOLTAGE ADJ. RANGE LINE REGULATION LOAD REGULATION SETUP, RISE TIME HOLD UP TIME (Typ.) VOLTAGE RANGE FREQUENCY RANGE POWER FACTOR (Typ.) INPUT EFFICIENCY (Typ.) AC CURRENT (Typ.) INRUSH CURRENT (Typ.) LEAKAGE CURRENT OVERLOAD PROTECTION OVER VOLTAGE OVER TEMPERATURE SDR-240-24 24V 10A 0 ~ 10A 240W 15A 360W (3sec.) 120mVp-p 48 ~ 55V 1.0% 0.5% 1.0% 3000ms, 60ms/115VAC at full load 20ms/115VAC at full load 124 ~ 370VDC 0.99/115VAC at full load 1.3A/230VAC 65A/230VAC SDR-240-48 48V 5A 0 ~ 5A 240W 7.5A
RIPPLE & NOISE (max.) Note.2 100mVp-p 24 ~ 28V VOLTAGE TOLERANCE Note.3 1.0% 0.5% 1.0% 1500ms, 60ms/230VAC 20ms/230VAC 88 ~ 264VAC 47 ~ 63Hz 0.93/230VAC
Note.8 94%
2.6A/115VAC 33A/115VAC <1mA / 240VAC
Normally works within 110 ~ 150% rated output power for more than 3 sec and then shut down o/p voltage with auto-recovery >150% rated power, constant current limiting with auto-recovery within 2 seconds and may cause to shut down if over 2 seconds 56 ~ 65V 29 ~ 33V Protection type : Shut down o/p voltage with auto-recovery 95 5 (TSW : detect on heatsink of power switch) Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
FUNCTION DC OK REALY CONTACT RATINGS (max.) 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load WORKING TEMP. Note.5 -25 ~ +70 (Refer to output load derating curve) 20 ~ 95% RH non-condensing WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS WITHSTAND VOLTAGE -20 ~ +85 , 10 ~ 95% RH 0.03%/ (0 ~ 50 Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 UL508, TUV EN60950-1 approved I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC / 70% RH
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 SAFETY & ISOLATION RESISTANCE EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B EMC (Note 4) Compliance to EN61000-3-2,-3 HARMONIC CURRENT EMS IMMUNITY MTBF OTHERS
NOTE
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A, SEMI F47, GL approved 169.3Khrs min. MIL-HDBK-217F (25 ) 63*125.2*113.5mm (W*H*D) 1.03Kg; 12pcs/13.4Kg/1.06CUFT
DIMENSION PACKING
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended. 6. 3 seconds max., please refer to peak loading curves. 7. Derating may be needed under low input voltage. Please check the derating curve for more details. 8. After 30 min. of burn-in.
File Name:SDR-240-SPEC 2008-12-17
240W Single Output Industrial DIN RAIL with PFC Function
Mechanical Specification
SDR-240 series
Case No. 979A Unit:mm
125.2
TB1
DC OK
TB2 1 2 3 4 5 6
1
63
2
DC OK
3
113.5
+V ADJ.
+
Terminal Pin No. Assignment (TB1)
Pin No. 1 2 3 Assignment FG AC/N AC/L
35
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
Terminal Pin No. Assignment (TB2)
Pin No. 1,2 3,4 5,6 Assignment Relay Contact DC OUTPUT +V DC OUTPUT -V
Block Diagram
DC OK
I/P
EMI FILTER & RECTIFIERS
PFC CIRCUIT
POWER SWITCHING
RECTIFIERS & FILTER O.C.P.
+V -V
U.V.P. FG PFC CONTROL
O.L.P. PWM & PFC CONTROL DETECTION CIRCUIT O.V.P.
DC OK Relay Contact
Contact Close Contact Open When the output voltage reaches the adjusted output voltage. When the output voltage drop below 90% output voltage.
Contact Ratings (max.) 30V/1A resistive load
File Name:SDR-240-SPEC 2008-12-17
240W Single Output Industrial DIN RAIL with PFC Function
Peak Loading
(1) 360W (2) 360W
SDR-240 series
240W 100 sec. 3 sec.
120W 10 sec. 3 sec.
Derating Curve
Output derating VS input voltage
150
100 90
112.5
For 3sec. (typ.)
80 70
100
LOAD (%)
LOAD (%)
40 50 60 70 (VERTICAL)
75
Continuous
60 50 40
60
-25
0
10
20
30
88
100
110
135
155
230
264
AMBIENT TEMPERATURE ( )
INPUT VOLTAGE (V) 60Hz
File Name:SDR-240-SPEC 2008-12-17


▲Up To Search▲   

 
Price & Availability of SDR-240

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X